Technical SpecificationsApplication Recommendation
Closed Cell NBR Rubber Foam Insulation
- The below average physical properties are values obtained in accordance with accepted test methods.
- At -40°C, Insulflex Closed Cell Insulation becomes hard and as temperature drops below -40°C will be increasingly brittle; however this hardening chracteristic does not affect thermal or water vapour permeability.
- The Fire rating standard method of tests conducted under controlled laboratory conditions is a measure of a material to spread flame when compared to a known standard and is not intended to reflect hazards presented by this or any material under actual fire conditions.
| Average Physical Properties | Rating | Test Method | |
|---|---|---|---|
| Density | 50 kg/m3 to 70 kg/m3 (Tubing) | ASTM D1667 | |
| 40 kg/m3 to 70 kg/m3 (Roll) | |||
| Thermal Conductivity ('K' Value) at 20˚C mean temperature | 0.034 W/mk | ASTM C518 | |
| Service Temperature C | -50˚C to + 105˚C | ASTM C534 | |
| Water Absorption (% by volume) | < 0.2% by volume | ASTM C209 | |
| Water Vapour Permeability | ≤ 1.73 x 10-14 g/Pa.m.s | ASTM E96 | |
| Water Vapour Resistance µ Factor | ≥ 10,000 | ASTM E96 | |
| Thermal Stability (% shrinkage) | 7 Days -50˚C | 0.20 % | ASTM C534 |
| 7 Days 105˚C | 3.30 % | ||
| Average Fire Propagation Average Surface Spread of Flame | Class 0 & Class 1 | BS 476 PART 6 & BS 476 PART 7 | |
| Flammability | V-0, 5VA, HF-1 | UL 94 | |
| Reaction To Fire | Self-Extinguishing, No Dripping | ||
| SIRIM QAS Listed Product | |||
| Fire & Rescue Department of Malaysia Approval Class 0 Product (BOMBA) | |||
| Singapore Certificate of Conformity (TUV/PSB Class 0) | |||
| Singapore Green Building Council (Awarded) | |||
| Green Building Council of Australia | |||
| REACH and RoHS (SGS) | |||
Thickness Recommendations To Control Condensation In Pipe Insulation Of Cooling Lines
- Insulation for pipes of 10mm ID to 76mm IPS are available in tubing form with wall thickness of up to 25mm.
- Insulation above 76mm IPS are in precut sheets and availble up to 38mm thickness.
- Insulflex thickness recommended within the specified temperature ranges will control condensation on indoor piping under design conditions defined as follows:
- MILD
- Air-Conditioned and arid areas.
- NORMAL
- Maximum severity of most indoor conditions seldom exceed 29.4°C and 70% RH.
- SEVERE & EXTREMELY SEVERE
- Conditions of high humidity or poorly ventilated areas where temperature may be depressed below the ambient.
Under conditions of high humidity, additional thickness of insulation may be required.
| DESIGN CONDITIONS | PIPE SIZE | PIPELINE TEMPERATURE | ||
|---|---|---|---|---|
| 14.4°C (58°F) |
7°C (44.6°F) |
2.5°C (36°F) |
||
| MILD CONDITION 26.7°C (80°F) 50% RH |
10MM ID TO 76MM IPS Above 76mm IPS to 127mm IPS Above 127mm IPS to 354mm IPS |
9mm 9mm 13mm |
9mm 13mm 13mm |
9mm 13mm 13mm |
| NORMAL CONDITION 29.4°C (85°F) 70% RH |
10MM ID TO 76MM IPS Above 76mm IPS to 127mm IPS Above 127mm IPS to 354mm IPS |
9mm 13mm 13mm |
13mm 13mm 13mm |
13mm 13mm 19mm |
| SEVERE CONDITION 32.2°C (90°F) 80% RH |
10MM ID TO 76MM IPS Above 76mm IPS to 127mm IPS Above 127mm IPS to 354mm IPS |
13mm 13mm 13mm |
19mm 25mm 25mm |
19mm 25mm |
Thickness Recommendations For Insulation Of Ductings, Tanks And Equipment Of Cooling Systems
| DESIGN CONDITIONS | PIPELINE TEMPERATURE | |||
|---|---|---|---|---|
| 15°C (59°F) | 12°C (53.6°F) | 7°C (44.6°F) | 2.5°C (36.5°F) | |
| 26.7°C (90°F) 50% RH |
9mm | 9mm | 13mm | 19mm |
| 29.4°C (85°F) 70% RH |
13mm | 13mm | 19mm | 25mm |
| 32.2°C (90°F) 80% RH |
13mm | 19mm | 25mm | 31mm |
| 32.2°C (90°F) 85% RH |
25mm | 25mm | 31mm | 38mm |